First-Order Plus Dead-Time Model: A Worked Example

Interpret gain, dead time and time constant from an original synthetic response, then separate model fitting from model validation.

State the model and its interpretation

A first-order plus dead-time model describes a response using a process gain K, a time constant τ and a dead time θ. In deviation variables, its transfer function is G(s) = K exp(−θs)/(τs + 1). It is a simplified representation, not proof that the physical process contains only one mechanism or one lag.

The example below is synthetic, linear and time invariant, with one input, one output and no added noise or competing disturbance. Its numbers are chosen to make the interpretation checkable.

Read the original synthetic step record

At time zero, the input changes from 10 to 12 input units. The output starts at 20 output units and eventually approaches 30. The response remains at its initial value until 4 seconds and then follows a first-order rise with an 8-second time constant.

Values generated from the stated synthetic model
Time after input change (s) Output units, approximately
0 20.000
4 20.000
8 23.935
12 26.321
20 28.647
28 29.502

For t ≥ 4 seconds, the constructed output is y(t) = 20 + 10[1 − exp(−(t − 4)/8)]. Before that delay, y(t) = 20. The formula generates this table; the table is not an independently measured validation dataset.

Calculate gain, delay and time constant

The input change is 12 − 10 = 2. The final output change is 30 − 20 = 10. Process gain is therefore K = 10/2 = 5 output units per input unit. The stated dead time is θ = 4 seconds.

One time constant after the delay, the output has completed about 63.2% of its final change. The corresponding level is 20 + 0.6321 × 10 ≈ 26.321, reached at t = 12 seconds. Therefore τ = 12 − 4 = 8 seconds. Subtracting the delay matters: 12 seconds is not the time constant in this example.

These values describe process response. They are not PID gain, integral time or recommended controller settings.

Check what a fitted step cannot establish

A real record may contain drift, noise, nonlinear response, simultaneous input changes or insufficient settling. Those conditions can make a visual first-order approximation misleading. An input change produced inside a feedback loop also needs its operating context; it is not automatically equivalent to this idealized input.

  • Record initial and final conditions and the input/output units.
  • Distinguish the input-change time from the first observable output response.
  • Check whether another input or disturbance changed during the record.
  • Use separate data and operating conditions to examine whether the model remains useful.
  • Inspect structured residuals and mismatched dynamics instead of relying only on visual fit.

This is a model-reading exercise, not an instruction to step an operating plant.

Continue from model interpretation to course selection

The system-identification guide separates estimation and validation. Review STA200 transfer-function identification training for the published syllabus. If your next subject is predictive control, compare the MPC horizon timing example without treating a single fitted curve as a ready-to-use controller model.